TL24A5T中文資料力特數(shù)據(jù)手冊PDF規(guī)格書
TL24A5T規(guī)格書詳情
Description
The TL Series provides protection against short cycling of a
compressor. At the end of each operation, or whenever power
is lost, a lockout delay is initiated. This lockout delay prevents
restarting of the compressor until the head pressure has
equalized. Compressor relay chatter due to thermostat bounce
is eliminated by use of optional one second delay-on-make. The
TL Series should not be used with cooling anticipator resistors
or solid-state switches. (See the TA Series).
Operation (Lockout)
Lockout: On initial closure of S1, the compressor relay energizes
immediately (or after an optional 1s delay). When the S1 opens
or input voltage is interrupted, the output opens and remains
open for the lockout time delay. During this lockout time delay
period, the compressor relay cannot be re-energized.
Reset: The lockout time delay cannot be reset. After the time
delay is completed, the unit automatically resets.
Features & Benefits
FEATURES BENEFITS
Lockout delay
Prevents rapid cycling of compressor and eliminates
nuisance service calls due to blown fuse or tripped
breaker by locked rotor during short cycling.
One second
Delay-on-Make
models ending in T)
Eliminates contactor chatter due to
thermostat bounce
Totally solid state
encapsulated
No moving parts to arc and wear out over time and
encapsulated to protect against shock, vibration,
and humidity
steady, 10A inrush,
solid state output Provides 100 million operations in typical conditions